A stable 24V DC power supply is essential for reliable communication, accurate signal acquisition, and consistent actuator operation in industrial automation systems. However, incorrect power supply sizing can lead to voltage drops, communication interruptions, unexpected module resets, and production downtime.
For machine builders, OEM manufacturers, and system integrators, calculating the required power supply capacity involves more than counting the number of installed I/O modules. Engineers must consider communication adapters, internal module consumption, sensors, actuators, cable resistance, simultaneous load conditions, and future expansion.
When designing distributed automation systems using Decowell I/O Modules, understanding the difference between system-side and field-side power is particularly important.
The basic sizing formula is:
Required Power Supply Current (A) = Maximum Simultaneous Load Current (A) × Design Margin Factor
For example, if a Remote I/O station requires 3.2 A under maximum continuous operating conditions, applying a 25% planning margin gives:
3.2 A × 1.25 = 4.0 A
A 24V DC, 5A power supply may be suitable, provided that its thermal derating, transient current capability, output regulation, and protection characteristics meet the actual installation requirements.
This guide explains the complete calculation process, using practical engineering examples and Decowell’s modular I/O architecture.
1. Why Is Correct 24V DC Power Supply Sizing Important?
Remote I/O stations are widely used in packaging machinery, automotive assembly lines, material handling equipment, automated warehouses, and industrial production systems.
These installations often contain multiple electrical loads with different current requirements.
An undersized power supply can cause:
- Communication interruptions: Voltage instability may cause network adapters to reset or disconnect.
- Unstable sensor operation: Insufficient supply voltage may affect sensor electronics and signal acquisition.
- Actuator switching failures: Solenoid valves and relay coils may fail to operate when voltage falls below their specified operating range.
- Unexpected production downtime: Intermittent power problems can be mistaken for PLC programming or network communication faults.
- Limited system expansion: Additional I/O modules or field devices may exceed the available power budget.
Excessive oversizing can also increase equipment costs and control cabinet space requirements.
The objective is to select a power supply that provides sufficient continuous current, handles transient loads, and maintains stable voltage under the expected operating conditions.
2. Identify All Electrical Loads in the Remote I/O Station
Before calculating power supply capacity, engineers should identify every component powered by the selected 24V DC source.
A typical distributed I/O station may include the following electrical loads.
| Component | Power Consumption Considerations |
|---|---|
| Communication adapter | Internal electronics and network interface |
| Digital input module | Module electronics and input-side power requirements |
| Digital output module | Module electronics and connected output loads |
| Analog input module | Signal conditioning and connected transmitters |
| Proximity sensor | Individual sensor operating current |
| Photoelectric sensor | Sensor electronics and output circuitry |
| Solenoid valve | Coil current and simultaneous activation |
| Relay | Coil consumption and switching characteristics |
| Industrial Ethernet equipment | Additional devices sharing the same supply |
One important engineering principle is to distinguish between module internal consumption and connected field-device current.
For example, a digital output module may consume relatively little power internally, while the solenoid valves connected to its outputs require significantly more current.
The module’s maximum output current rating indicates the allowable connected load. It does not necessarily represent the current continuously consumed by the module itself.
Therefore, engineers should calculate actual connected loads rather than automatically adding every output channel’s maximum rating.
3. Understand System-Side and I/O-Side Power Requirements
Modular Remote I/O systems may separate internal electronics power from field-side power distribution.
This distinction is essential for accurate 24V DC power supply sizing.
3.1 System-Side Power
System-side power typically supplies:
- Communication adapter electronics
- Internal communication circuits
- Module logic circuits
- Internal bus functions
Some modular architectures convert the incoming 24V DC supply into a lower voltage for internal logic operation.
3.2 I/O-Side Power
Depending on the product architecture, I/O-side power may supply:
- Digital input field circuits
- Connected industrial sensors
- Digital output loads
- Solenoid valves and relay coils
- Other field devices
System-side and I/O-side power may use separate terminals, even when both operate from a nominal 24V DC supply.
3.3 Decowell EX Series Power Architecture
The Decowell EX I/O Module Series provides a practical example of modular industrial I/O power distribution.
The EX series supports digital input/output, analog input/output, temperature acquisition, and other expansion modules.
For the EX-1010 DeviceNet adapter, published specifications include:
| Parameter | Specification |
|---|---|
| System-side supply voltage | DC 24V, 18–36V |
| Maximum system-side supply current | 2 A |
| I/O-side supply voltage | DC 24V ±20% |
| Maximum I/O-side output current | 10 A |
| Maximum expansion modules | 32 |
These values represent specified electrical limits and should not be interpreted as the actual current consumed by every EX-series station.
For example, a 10 A I/O-side current rating does not mean the station continuously draws 10 A.
Actual current depends on the installed modules, connected sensors, actuators, and operating conditions.
Decowell’s EX-1010 DeviceNet Network Setup Guide also describes the separate system-side and I/O-side power terminals.
The EX-1010 uses:
- 1L+ and 1M for system-side power
- 2L+ and 2M for I/O-side power
The guide recommends using separate power-line groups from the same 24V DC source to reduce interference from changing I/O loads.
This arrangement illustrates why engineers must verify the current requirements of each power domain independently.
4. How to Calculate Total 24V DC Power Supply Current
The complete calculation can be divided into four steps.
Step 1: Calculate Internal Module Consumption
Identify the specified current consumption of the communication adapter and each expansion module.
For modules powered directly from 24V DC:
I_modules = I_adapter + I_module1 + I_module2 + … + I_moduleN
Where:
- I_modules = Total module input current
- I_adapter = Communication adapter current
- I_moduleN = Individual expansion module current
For modules using internal voltage conversion, engineers should use the manufacturer’s specified 24V input current or calculate input power while accounting for conversion efficiency.
Do not directly add 5V logic current to 24V input current.
Step 2: Calculate Sensor Current
Calculate the combined current consumption of all sensors supplied by the same power source.
I_sensors = Number of Sensors × Current per Sensor
Example:
- Number of proximity sensors: 16
- Current per sensor: 15 mA
Total sensor current:
16 × 15 mA = 240 mA
I_sensors = 0.24 A
If different sensor types are installed, calculate each group separately.
Step 3: Calculate Output Load Current
Output devices can account for a substantial portion of the total power requirement.
Consider a station with:
- 8 solenoid valve coils
- Current per coil: 120 mA
- Maximum simultaneous activation: 8 coils
Total output current:
8 × 120 mA = 960 mA
I_outputs = 0.96 A
If fewer coils can operate simultaneously, a lower current budget may be justified, provided that the maximum concurrency is verified under normal operation, startup, manual control, and relevant fault conditions.
Step 4: Add an Appropriate Design Margin
Once the maximum simultaneous load current is calculated, engineers should apply a suitable planning margin.
For preliminary design, a margin of approximately 20–30% may be useful, but it is not a universal engineering requirement.
For a 25% allowance:
I_required = I_total × 1.25
The final power supply must also satisfy startup current, thermal derating, voltage regulation, and protection requirements.
5. Practical Example: 24V DC Power Supply Sizing for an Automated Packaging Station
Consider a hypothetical automated packaging station equipped with a modular Remote I/O system.
The station includes a communication adapter, digital input modules, digital output modules, proximity sensors, and solenoid valves.
The following figures are illustrative calculation assumptions rather than measured Decowell product consumption values.
| Electrical Component | Quantity | Current per Unit | Total Current |
|---|---|---|---|
| Communication adapter | 1 | 0.20 A | 0.20 A |
| Digital input modules | 2 | 0.08 A | 0.16 A |
| Digital output modules | 2 | 0.10 A | 0.20 A |
| Proximity sensors | 16 | 0.015 A | 0.24 A |
| Solenoid valve coils | 8 | 0.12 A | 0.96 A |
| Total | 1.76 A |
In this example, all listed currents are assumed to be drawn from the same 24V DC source, and no electrical load is counted twice.
Calculate the Required Current
Total continuous load:
1.76 A
Apply a 25% design margin:
1.76 × 1.25 = 2.20 A
Therefore, the preliminary required capacity is 2.20 A.
A 24V DC, 3A power supply could be considered if its performance meets the complete operating requirements.
Its nominal power capacity is:
24V × 3A = 72W
For modular systems with separate power domains, engineers should calculate system-side and I/O-side current budgets individually before selecting the external power supply.
6. How Does Cable Voltage Drop Affect Power Supply Capacity?
Selecting a power supply with sufficient current capacity does not guarantee that every Remote I/O module receives adequate voltage.
Long cables, small conductor sizes, and high load currents can create voltage drops between the power supply and the field station.
For a basic two-conductor DC circuit:
Voltage Drop (V) = 2 × Cable Length × Current × Conductor Resistivity / Conductor Area
Where:
- Cable length is the one-way distance in meters.
- Current is measured in amperes.
- Resistivity is measured in Ω·mm²/m.
- Conductor area is measured in mm².
Example Calculation
Assume:
- One-way cable length: 20 m
- Load current: 3 A
- Copper conductor area: 1.5 mm²
- Copper resistivity: approximately 0.0175 Ω·mm²/m at 20°C
Voltage drop:
2 × 20 × 3 × 0.0175 / 1.5 = 1.4V
If the power supply output is 24V:
24V − 1.4V = 22.6V
The estimated receiving-end voltage is approximately 22.6V before connector and terminal losses.
Actual voltage drop may be higher at elevated cable temperatures.
To reduce voltage drop, engineers may:
- Increase conductor cross-sectional area.
- Shorten power cable runs.
- Install distributed power supplies closer to the loads.
- Separate high-current actuators from sensitive electronics.
- Verify voltage at the Remote I/O terminals under maximum operating load.
7. Decowell RB-0100 Power Module: Power Distribution Considerations
The Decowell RB-0100 Power Supply Module is designed for power distribution within the RB modular I/O architecture.
According to published product information, the RB-0100 includes the following electrical characteristics:
| Parameter | RB-0100 Specification |
|---|---|
| System supply voltage | 24V |
| Logic output voltage | 5V |
| Logic output current | 2 A |
| I/O terminal voltage | 24V |
| I/O terminal current | 10 A |
| Protection class | IP20 |
| Operating temperature | -25°C to +60°C |
The RB-0100 converts a 24V input into 5V logic power and supports I/O terminal power distribution.
Why Is This Important for Power Supply Sizing?
Engineers must distinguish between internal logic power and field-side current.
The 5V logic output capacity should not be added directly to the 24V field current rating.
Instead, engineers should:
- Calculate the actual logic-side power demand.
- Account for internal voltage conversion efficiency.
- Calculate the field-side load current.
- Verify the module’s current distribution limits.
- Select an external supply that supports the complete system.
For example, a 5V logic circuit consuming 1A requires:
5V × 1A = 5W
If the converter operates at an assumed efficiency of 85%, the corresponding input power would be:
5W / 0.85 = 5.88W
At a 24V input:
5.88W / 24V ≈ 0.245A
This example demonstrates why input power calculations are more accurate than directly combining current values from different voltage levels.
The assumed efficiency is illustrative and must be replaced with verified product data when available.
8. Common Mistakes in Remote I/O Power Supply Selection
Mistake 1: Calculating Only Module Consumption
Some designers calculate the current consumption of communication adapters and expansion modules but ignore connected sensors and actuators.
Solution: Include every load supplied by the selected 24V DC source.
Mistake 2: Treating Maximum Output Ratings as Continuous Consumption
A digital output channel rated for 0.5A does not necessarily consume 0.5A during operation.
Solution: Use actual connected load specifications and validated simultaneous operating conditions.
Mistake 3: Ignoring Startup Current
Solenoid valves, relays, and other industrial devices may produce transient current demands.
Solution: Check peak current requirements and the power supply’s overload response.
Mistake 4: Ignoring Control Cabinet Temperature
Power supply output capacity may decrease at elevated operating temperatures.
Solution: Review the manufacturer’s thermal derating specifications.
Mistake 5: Ignoring Internal Power Distribution Limits
A 24V DC power supply rated at 10A does not mean every terminal or I/O module can safely carry 10A.
Solution: Verify the current rating of each connector, terminal, output group, and power distribution module.
Mistake 6: Failing to Plan for Expansion
Future sensors or I/O modules may increase the electrical load.
Solution: Reserve appropriate capacity for anticipated system upgrades without ignoring the limits of the existing power distribution architecture.
9. Engineering Checklist Before Selecting a 24V DC Power Supply
Before finalizing the power supply selection, verify the following requirements:
| Inspection Item | Engineering Requirement |
|---|---|
| Operating voltage | Within the specified module input range |
| Adapter consumption | Based on manufacturer documentation |
| Expansion module consumption | Calculated for the complete station |
| Sensor current | Based on actual connected devices |
| Output load current | Based on maximum simultaneous operation |
| Cable voltage drop | Within acceptable receiving-end voltage limits |
| Startup current | Supported by power supply transient capability |
| Temperature derating | Checked against installation conditions |
| Circuit protection | Coordinated with wiring and device ratings |
| Future expansion | Included where required by project planning |
For product-specific electrical information, engineers should consult the Decowell Product User Manuals.
These resources provide wiring information, terminal definitions, configuration instructions, and product-specific technical guidance.
Manufacturer documentation should always take precedence over generic sizing assumptions.
10. Frequently Asked Questions
How many Remote I/O modules can a 24V 5A power supply support?
There is no fixed module quantity.
The number depends on the current consumption of each module, connected field devices, power distribution limits, and operating conditions.
A 24V 5A supply has a nominal capacity of 120W, but the usable capacity depends on thermal derating and other electrical requirements.
Should sensors and solenoid valves use separate power supplies?
Separate supplies or separately protected power branches may improve system robustness when high-current switching loads could disturb sensitive electronics.
The final decision depends on the electrical architecture, isolation requirements, and connected load characteristics.
Can an oversized power supply damage Remote I/O modules?
A properly regulated 24V DC power supply with a higher current rating does not force its maximum rated current into a normally operating load.
However, correct voltage, polarity, circuit protection, and fault-current coordination remain essential.
Is a 25% power supply margin always sufficient?
No.
A 25% margin is only a preliminary planning assumption.
The actual requirement depends on startup current, voltage drop, operating temperature, expansion needs, and the manufacturer’s electrical specifications.
What happens if the Remote I/O power supply is overloaded?
Depending on the power supply design, overload conditions may result in voltage reduction, current limiting, protective shutdown, or repeated restart attempts.
These conditions may cause module resets, communication interruptions, and output failures.
Conclusion: Reliable Remote I/O Systems Begin with Correct Power Planning
Accurate 24V DC power supply sizing requires a complete understanding of the electrical loads within a distributed I/O station.
Engineers should calculate communication adapter consumption, expansion module requirements, sensor current, actuator loads, simultaneous operating conditions, cable voltage drop, and appropriate design margins.
For modular systems such as the Decowell EX and RB series, it is equally important to distinguish between internal logic power and field-side power distribution.
Correct power planning helps reduce voltage-related failures, improve system reliability, simplify commissioning, and support future equipment expansion.
Need Assistance with Remote I/O Power Supply Selection?
Decowell provides modular industrial I/O solutions for machine builders, OEM manufacturers, and automation system integrators.
Share your PLC communication protocol, required I/O points, sensor and actuator specifications, and 24V DC power arrangement with our technical team to discuss a suitable I/O configuration.
Explore the Decowell EX I/O Module Series or contact Decowell for technical support.



